Heat Load - Highlight Series L.E.D Lighting 800x500

Download the PDF

Highlight Series M/T (Non Heated Glass)

800mm H x 500mm Double Glazed Non Heated
Glass Medium Temperature
1 Door 2 Door 3 Door 4 Door 5 Door 6 Door 7 Door 8 Door
Store Conditions 25˚C & 60% RH 79 145 210 276 341 406 472 537
NON-HEATED GLASS DOORS AIR CONDITIONED APPLICATIONS 25˚C & 60% RH ONLY

Highlight Series M/T 'Mullionless' (Non Heated Glass)

800mm H x 500mm Double Glazed Non Heated
Glass Medium Temperature
1 Door 2 Door 3 Door 4 Door 5 Door 6 Door 7 Door 8 Door
Store Conditions 25˚C & 60% RH 70 125 181 237 293 348 404 459
NON-HEATED GLASS DOORS AIR CONDITIONED APPLICATIONS 25˚C & 60% RH ONLY

Highlight Series L/T (Non Heated Glass)

800mm H x 500mm Double Glazed Non Heated
Glass Medium Temperature
1 Door 2 Door 3 Door 4 Door 5 Door 6 Door 7 Door 8 Door
Store Conditions 25˚C & 60% RH 116 211 305 400 484 589 684 778
NON-HEATED GLASS DOORS AIR CONDITIONED APPLICATIONS 25˚C & 60% RH ONLY

Tropical Highlight Series M/T (Heated Glass)

800mm H x 500mm Double Glazed Heated Glass
Medium Temperature
1 Door 2 Door 3 Door 4 Door 5 Door 6 Door 7 Door 8 Door
Store Conditions 25˚C & 60% RH 89 163 238 313 388 462 537 611
Store Conditions 30˚C & 70% RH 97 180 262 346 429 511 594 677
Store Conditions 35˚C & 70% RH 108 202 295 390 484 577 671 765
Store Conditions 40˚C & 70% RH 121 227 334 442 548 655 762 868

Tropical Highlight Series M/T 'Mullionless' (Heated Glass)

800mm H x 500mm Double Glazed Heated Glass
Medium Temperature
1 Door 2 Door 3 Door 4 Door 5 Door 6 Door 7 Door 8 Door
Store Conditions 25˚C & 60% RH 90 166 241 318 394 470 545 621
Store Conditions 30˚C & 70% RH 99 184 269 356 441 526 611 696
Store Conditions 35˚C & 70% RH 110 206 302 400 496 592 688 784
Store Conditions 40˚C & 70% RH 123 232 241 451 561 670 779 888

Tropical Highlight Series Low Temperature (Heated Glass)

800mm H x 500mm Double Glazed Heated Glass
Medium Temperature
1 Door 2 Door 3 Door 4 Door 5 Door 6 Door 7 Door 8 Door
Store Conditions 25˚C & 60% RH 130 238 347 456 564 672 781 890
Store Conditions 30˚C & 70% RH 142 263 384 505 626 746 867 989
Store Conditions 35˚C & 70% RH 159 297 435 573 710 848 986 1125
Store Conditions 40˚C & 70% RH 179 337 495 653 810 968 1126 1285