Heat Load - Standard Series L.E.D Lighting 1800x500
Standard Series M/T (Non Heated Glass) |
||||||||
| 1800mm H x 500mm Double Glazed Non Heated Glass Medium Temperature |
1 Door | 2 Door | 3 Door | 4 Door | 5 Door | 6 Door | 7 Door | 8 Door |
|---|---|---|---|---|---|---|---|---|
| Store Conditions 25˚C & 60% RH | 253 | 414 | 576 | 738 | 899 | 1060 | 1222 | 1384 |
| NON-HEATED GLASS DOORS AIR CONDITIONED APPLICATIONS 25˚C & 60% RH ONLY | ||||||||
Standard Series M/T 'Mullionless' (Non Heated Glass) |
||||||||
| 1800mm H x 500mm Double Glazed Non Heated Glass Medium Temperature |
1 Door | 2 Door | 3 Door | 4 Door | 5 Door | 6 Door | 7 Door | 8 Door |
|---|---|---|---|---|---|---|---|---|
| Store Conditions 25˚C & 60% RH | 217 | 343 | 469 | 595 | 720 | 846 | 972 | 1098 |
| NON-HEATED GLASS DOORS AIR CONDITIONED APPLICATIONS 25˚C & 60% RH ONLY | ||||||||
Standard Series M/T (Heated Glass) |
||||||||
| 1800mm H x 500mm Double Glazed Heated Glass Medium Temperature |
1 Door | 2 Door | 3 Door | 4 Door | 5 Door | 6 Door | 7 Door | 8 Door |
|---|---|---|---|---|---|---|---|---|
| Store Conditions 25˚C & 60% RH | 296 | 501 | 706 | 910 | 1114 | 1320 | 1524 | 1729 |
| Store Conditions 30˚C & 70% RH | 325 | 560 | 764 | 1028 | 1262 | 1497 | 1731 | 1965 |
| Store Conditions 35˚C & 70% RH | 347 | 604 | 860 | 1116 | 1371 | 1628 | 1884 | 2140 |
| Store Conditions 40˚C & 70% RH | 374 | 657 | 940 | 1222 | 1504 | 1788 | 2071 | 2353 |
Standard Series M/T 'Mullionless' (Heated Glass) |
||||||||
| 1800mm H x 500mm Double Glazed Heated Glass Medium Temperature |
1 Door | 2 Door | 3 Door | 4 Door | 5 Door | 6 Door | 7 Door | 8 Door |
|---|---|---|---|---|---|---|---|---|
| Store Conditions 25˚C & 60% RH | 276 | 462 | 647 | 831 | 1016 | 1201 | 1386 | 1572 |
| Store Conditions 30˚C & 70% RH | 308 | 524 | 741 | 957 | 1172 | 1389 | 1606 | 1822 |
| Store Conditions 35˚C & 70% RH | 329 | 568 | 806 | 1044 | 1282 | 1520 | 1759 | 1997 |
| Store Conditions 40˚C & 70% RH | 356 | 621 | 886 | 1151 | 1415 | 1680 | 1945 | 2210 |
Standard Series Low Temperature (Heated Glass) |
||||||||
| 1800mm H x 500mm Double Glazed Heated Glass Medium Temperature |
1 Door | 2 Door | 3 Door | 4 Door | 5 Door | 6 Door | 7 Door | 8 Door |
|---|---|---|---|---|---|---|---|---|
| Store Conditions 25˚C & 60% RH | 473 | 829 | 1187 | 1544 | 1901 | 2259 | 2616 | 2973 |
| Store Conditions 30˚C & 70% RH | 520 | 923 | 1327 | 1732 | 2136 | 2540 | 2944 | 3348 |
| Store Conditions 35˚C & 70% RH | 553 | 989 | 1426 | 1863 | 2300 | 2737 | 3175 | 3611 |
| Store Conditions 40˚C & 70% RH | 591 | 1067 | 1543 | 2019 | 2495 | 2971 | 3447 | 3923 |
Home / Product Guide / About Us / Downloads / Technical Data / Contact Us